Coordinated switchgear-bay equipment comprising SF6 and vacuum circuit breakers for fault interruption, together with current (CT) and voltage (VT/PT) instrument transformers and MV HRC fuses for protection and metering. Vacuum interrupters serve indoor MV switchgear and SF6 puffer chambers outdoor HV applications; CTs and VTs scale primary current and voltage to standardised secondary values per IEC 61869, with metering and protection accuracy classes to suit revenue metering and relay schemes.
Product image pending
HV & MV/LV Power Distribution Equipment
Circuit Breakers, Fuses, Current Transformers (CTs) & Voltage Transformers (VTs/PTs)
| Voltage class | HV up to 170 kV |
|---|---|
| Rating | CB 12–170 kV / 630–4000 A / 25–63 kA; CT/VT to IEC 61869; HRC fuses up to 40.5 kV |
| Insulation / medium | SF6 / Oil |
| Standards | IEC 62271-100, IEC 61869-1, IEC 61869-2, IEC 61869-3, IEC 60282-1 |